Polymer rod post insulator IPRP-6-330/1300 is to be used for insulation and protection of current-carrying units in electric devices, electricity distribution plants, switch substations with 330 kV voltage as rotary insulating element, supporting conductor lines and «knives» of outside plant disconnectors, and as a part of bus rod support.
Polymer insulator IPRP-6-330/1300 is a modern alternative to traditional ceramic and porcelain insulators.
|
IPRP-6-330/1300 |
Rated voltage, kV |
330 |
Full lightning impulse testing voltage, not less, kV |
1300 |
Minimal bending failure, kN |
6 |
Leakage distance, cm |
905 |
Weight, kg |
180 |
|
|